Testing portfolio
Wide range of possibilities
Besides high voltage testing, other examinations can be performed, among them measurements of conventional and UHF partial discharge (PD) radio interference voltage (RIV), measurements of dissipation factor and capacity, and rain tests. If required, monitoring camera systems and microscopes are used. In addition to the high voltage testing, the open-air testing area permits long-term insulation testing under DC and AC to simulate aging processes. The large test halls of the high-voltage testing laboratory are shielded. This makes sensitive PD measurements with a very low noise level of less than 1 pC possible. The high-voltage testing laboratory also permits tests for switching of bus-charging currents by GIS disconnectors. Furthermore, surge current test circuits for surge arrester tests are availableAbstract from the testing portfolio of the high-voltage testing laboratory
- Lightning impulse voltage
- Alternating voltage
- Direct voltage
- Switching impulse voltage
- Combined voltage tests
- Long-term tests of insulation materials under DC and AC
- Conventional and UHF partial discharge measurement (PD)
- Radio interference voltage tests (RIV)
- Measurements of dissipation factor and capacity
- Rain tests
Specifications
Maximum test voltages
Alternating voltage (50 Hz)
1,200 kV, open air up to 1,800 kV
Lightning impulse voltage (1.2/50 µs)
3,000 kV
Switching impulse voltage (250/2,500 µs)
1,800 kV
Direct voltage
1,200 kV
Maximum impulse currents
Maximum lightning impulse current (8/20 µs)
40 kA
Maximum switching impulse current (30/60 µs)
3 kA
Maximum high current impulse (4/10 µs)
150 kA
Maximum long-duration current impulse (2 ms)
5 kA, rectangular impulse