Siemens Energy has developed a device in which the isolating distance has been integrated in the SF6 gas compartment in order to reduce external environmental influences. The DCB (Disconnecting Circuit Breaker) is used as a circuit breaker and also as a disconnector – two functions combined in one device. An additional air-insulated earthing switch can be mounted onto the supporting structure for voltages up to 145 kV.
3AP1 DCB | 3AP2 DCB | |
---|---|---|
Rated voltage [kV] | 145 | 420 |
Number of interrupter units per pole | 1 | 2 |
Rated power-frequency withstand voltage [kV] | 275 or 315 | 520 or 610 |
Rated lightning impulse withstand voltage / min [kV] | 650 or 750 | 1425 or 1665 |
Rated switching impulse withstand voltage [kV] | 1050 or 1245 | |
Rated normal current, up to [A] | 4000 | |
Rated short-time withstand current (1s - 3s), up to [kA (rms)] | 40 | |
Temperature range [°C] | -40 up to +40 | |
Rated operating sequence | 0-0.3 s-CO-3 min-CO or CO-15 s-CO | |
Rated break time | 3 cycles | |
Rated frequency [Hz] | 50 or 60 | |
Maintenance after | 25 years | |
Insulating medium | SF6 |
You can find details on our Dead Tank Compact circuit breakers and information about our services here.
We can gladly help you with installation, commissioning, diagnostics and malfunctions